Inputs/Outputs
NOTE: To disable an input metering channel and remove any port associations, set Assigned
Input to No connection.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Click Energy Applications > Digital Input Based.
4. Select the input metering channel you want to configure and click Edit. The Input Metering
Channel Setup screen is displayed.
5. Select Enabled to enable the input metering feature.
6. Click Select to define which digital input is the pulse source for the input metering channel.
7. Clear the Standard quantity check box. The screen changes to display custom input
metering parameters.
8. Configure the remaining parameters as required.
9. Click OK to save your configuration.
10. Configure your meter to log the input metering data if required.
Parameter
Pulse Weight
Units
Demand Period
Rate
Scaling
Time Base

Digital outputs

Digital output applications

Digital outputs are typically used in switching applications, for example, to provide on/off control
signals for switching capacitor banks, generators, and other external devices and equipment.
The digital output can also be used in demand synchronization applications, where the meter
provides pulse signals to the input of another meter to control its demand period. The digital
output can also be used in energy pulsing applications, where a receiving device determines
energy usage by counting the kWh pulses coming from the meter's digital output port.

Configuring onboard digital outputs using ION Setup

To configure the meter's digital outputs using ION Setup:
141
Description
Enter the value per pulse.
Select the measurement units associated with the pulse.
Note: Include source identification information by entering "@" followed by
the source identifier.
Enter the frequency in minutes that input metering data is calculated in your
energy management system.
Select the rate associated with the defined Units.
Select the scaling value based on the relationship between Units and Rate.
Select the value and units to match the Rate.