Configuring Standard Security Using Ion Setup - Siemens 9410 Series User Manual

Hide thumbs Also See for 9410 Series:
Table of Contents

Advertisement

9410 series

Configuring standard security using ION Setup

48
You can fully configure standard and advanced security on your meter using ION
Setup.
In order to change security settings, you must be logged into ION Setup with an
appropriate ION Setup user level. You must also have the appropriate meter-level
security access to configure meter security.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to Security. Select Security Mode and click Edit. The open dialog box
appears.
4. Select the appropriate security configuration file (*.scf) to configure your meter:
– Standard: allows you to configure basic security and communications protocol
lockout.
– Advanced: includes the standard security features and adds user access/
password security settings.
5. The standard options or advanced options configuration screen appears.
Configure the security parameters as required, some parameters can only be
configured using advanced security.
Click Next to configure protocol access information. The protocol lockout screen is
displayed.
6. In the protocol lockout screen select the protocols that you want to be protected by
the protocol lockout function. Select each protocol and click Edit to configure the
protocol-specific parameters.
7. Enter the lockout duration (in minutes).
8. Click Events to configure user access event priorities. The Event Priorities screen
appears.
9. Configure the user access event priorities.
Security
7EN05-0336-03