Technical Data; Input; Power Supply; Performance Characteristics - Endress+Hauser RIA15 Operating Instructions Manual

Process indicator
Table of Contents

Advertisement

Technical data

Measured variable
Measuring range
Supply voltage
Reference operating
conditions
Maximum measured error
Resolution
Influence of ambient
temperature
Warm-up period
26
12
Technical data
12.1

Input

Voltage drop
Standard device with 4 to 20 mA communication
Display lighting
The 4 to 20 mA current signal is the input variable.
HART
®
signals are not affected.
4 to 20 mA (scalable, reverse polarity protection)
Max. input current 200 mA
12.2

Power supply

NOTICE
SELV/Class 2 device
The device may be powered only by a power unit with an energy-limited circuit in
accordance with UL/EN/IEC 61010-1 Paragraph 9.4 or Class 2 as per UL 1310: ' S ELV
or Class 2 circuit' .
The process indicator is loop-powered and does not require any external power supply. The
voltage drop is1 V in the standard version with 4 to 20 mA communication and an
additional 2.9 V if display lighting is used.
12.3

Performance characteristics

Reference temperature 25 °C ±5 °C (77 °F ±9 °F)
Humidity 20 to 60 % relative humidity
Input
Range
Current
4 to 20 mA
Over range up to 22 mA
Signal resolution > 13 bit
< 0.02 %/K (0.01 %/°F) of measuring range
10 minutes
≤ 1.0 V
Additional 2.9 V
Measured error of measuring range
±0.1 %
RIA15