Technical Data; Technical Data At A Glance - Endress+Hauser prosonic M FMU 40 Operating Instructions Manual

With hart and 4 ... 20 ma ultrasonic level measurement
Hide thumbs Also See for prosonic M FMU 40:
Table of Contents

Advertisement

Prosonic M FMU 40/41/43 with HART and 4 ... 20 mA
Measured variable
Maximum range/blocking
distance
Output signal
Signal on alarm
Cable entry
Supply voltage
10

Technical Data

10.1

Technical data at a glance

10.1.1
Input
The distance D between the sensor membrane and the product surface is measured.
Using the linearisation function, the device uses D to calculate:
• level L in any units
• volume V in any units
• flow Q across measuring weirs or open channels in any units
Sensor
Maximum range in liquids
FMU 40
5 m
FMU 41
8 m
FMU 43
15 m
1
The actual range is dependent on the measuring conditions. Refer to Technical
Information TI 365F/00/en for an estimation.
10.1.2
Output
4 ... 20 mA with HART protocol
• Error symbol, error code and plain text description on the on-site display
• Error code via HART communication
• Current output (configurable)
10.1.3
Auxiliary energy
• Cable gland M20x1.5 (recommended cable diameter 6 ... 10 mm)
• Cable entry G½ or ½ NPT
• Loop-powered HART: 14 ... 36 V (depending on output current)
• Loop-powered fixed current: 10 ... 36 V
• 4-wire DC: 10.5 ... 32 VDC
• 4-wire AC: 90 ... 253 VAC
There may be additional restrictions for devices with an explosion protection certificate.
Refer to the notes in the appropriate safety instructions (XA).
1
Maximum range in solids
2 m
3,5 m
7 m
Technical Data
1
blocking distance
0,25 m
0,4 m
0,6 m
53

Advertisement

Table of Contents
loading

This manual is also suitable for:

Prosonic m fmu 41Prosonic m fmu 43