Daikin RXM20R Service Manual page 116

Hide thumbs Also See for RXM20R:
Table of Contents

Advertisement

4
|
Components
Problem solved?
Service manual
116
A
a
A Wall mounted indoor unit
a Fuse F1U
A
A Floor standing indoor unit
a Fuse F1U
Blown fuse on the indoor unit power
PCB?
Yes
No
After all checking procedures listed above have been performed:
Is the problem solved?
Yes
No
a
Action
Replace the blown fuse, see
"4.10.2 Repair
procedures" [
Return to
"4.9.1 Checking
4
procedures" [
 106] of the indoor unit
power PCB and continue with the next
procedure.
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
RXM20~71R(9) + ARXM25~71R(9) + FTXM20~71R + ATXM25~50R +
4
 117].
FVXM25~50A
Split New Perfera R32
ESIE20-11B – 2022.02

Advertisement

Table of Contents
loading

Table of Contents