4
|
Components
To remove the top plate
To remove the front plate
Service manual
154
INFORMATION
This procedure is just an example and may differ on some details for your actual unit.
Prerequisite: Stop the unit operation via the user interface.
1 Turn OFF the respective circuit breaker.
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
2 Loosen and remove the screws that fix the top plate.
a
b
a
a Screw
b Top plate
3 Remove the top plate.
INFORMATION
This procedure is just an example and may differ on some details for your actual unit.
Prerequisite: Remove the top plate, see
1 Loosen and remove the screws that fix the front plate.
2
1
1
1
2
a
a
a
a
"4.14 Plate
work" [
RXM20~71R(9) + ARXM25~71R(9) + FTXM20~71R + ATXM25~50R +
4
 153].
FVXM25~50A
Split New Perfera R32