Sinclair SDV 6 User & Installation Manual page 66

Commercial air conditioners
Hide thumbs Also See for SDV 6:
Table of Contents

Advertisement

SDV6 protocol
IDU set
Parameter name
item
Static pressure setting
of IDU
High ceiling setting
On-site air flow adjustment
factor
On-site
set item
Q4/Q4 min air outlet closed 1
Q4/Q4 min air outlet closed 2
Q4/Q4 min air outlet closed 3
Q4/Q4 min air outlet closed 4
Cooling/heating only for IDU
One-to-many of WDC enabled
IDU buzzer
IDU
setting
EXV opening selection
during heating standby
Parameter range
The IDU sets the static pressure
00/01~19/FF
based on the set gear, FF (VRF
unit: main board DIP of IDU;
other models: reserved)
00/01/02
00: 3 m; 01: 4 m;
02: 4.5 m
Note: Not supported on FAPUs.
00/01/02/03/
00:1;
04/05/06
03:1.15; 04:0.95;
06:0.85
00/01
00: Free control; 01: Close
00/01
00: Free control; 01: Close
00/01
00: Free control; 01: Close
00: Free control; 01: Close
00/01
00/01
00: Cooling and heating;
01: Cooling only
00/01
00: No; 01: Yes
00/01/02
00: Not sound; 01: Sound;
02: Display panel only
00/01/02/14
00: 56P; 01: 72P;
02: 00P; 14: Auto regulation
63
Remarks
01:1.05;
02: 1.1;
05:0.9;