IDU set
Parameter name
item
IDU's anti-cold wind
temperature setting in
heating mode
Anti-cold wind temperature
setting of special IDUs
Temp.
setting
Cooling return difference
temp.
IDU heating temp.
compensation
Parameter range
00/01/02/03/FF
Common IDUs (models 1, 3,
4, 6, and 8):
00: 15; 01: 20; 02: 24;
03: 26; FF: Invalid
FAPU (models 2 and 7):
00: 14; 01: 12; 02: 16;
03: 18; FF: Reserved
Note: Not supported on FAPUs.
00/01/02/03: corresponds to different
00/01/02/03/F
values; 04: anti-cold wind invalid
This setting item is displayed in the
anti-cold wind setting of special IDUs
such as FAPUs and AHU-KITs
00: 1°C; 01: 2°C; 02: 0.5°C;
00/01/02/03/04
03: 1.5°C; 04: 2.5°C
Note: Not supported on FAPUs.
VRF unit: 00: 6°C; 01: 2°C;
00/01/02/03/04/
FF
02: 4°C; 03: 6°C;
04: 0°C; FF: main board DIP
of master IDU
Split uni: 00: 6°C; 01: 2°C;
02: 4°C; 03: 8°C;
04: 0°C; FF: reserved
Mini VRF unit: 00: 6°C;
01: 2°C; 02: 4°C; 03: 8°C;
04: 0°C; FF: Reserved
Note: Not supported on FAPUs.