Sinclair SDV 6 User & Installation Manual page 65

Commercial air conditioners
Hide thumbs Also See for SDV 6:
Table of Contents

Advertisement

IDU set
Parameter name
item
IDU cooling temp.
compensation
Temp.
setting
Sterilization setting
Other
settings
Drying time at
self-cleaning
Initial static pressure
Energy
detection
conservation
option
Fresh air dry contact 1 - fan
Fresh air dry contact 2 -
FAPU
economizer
setting
Fresh air dry contact 3 -
humidifier
Parameter range
VRF unit:
VRF unit: 00: 0°C; 01: 2°C;
00/01/FF
FF: main board DIP of IDU
Split unit:
Split uni: 00: 0°C; 01: 1°C;
00/01/02/03/FF
02: 2°C; 03: 3°C; FF: Reserved
Mini VRF unit:
Mini VRF unit: 00: 0°C; 01: 1°C;
00/01/02/03/04/
02: 2°C; 03: 3°C;
FF
04: -1°C; FF: Reserved
Note: Not supported on FAPUs.
00/01
00: Sterilization unavailable;
01: Plasma sterilization
00/01/02/03
00: 10 min; 01: 20 min;
02: 30 min; 03: 40 min
Note: Not supported on FAPUs.
00/01
00: Not reset initial static pressure;
01: Reset initial static pressure
Note: Not supported on FAPUs.
00/01
00: Disconnect; 01: Enable
Note: Not supported on FAPUs.
00/01
00: Disconnect; 01: Enable
Note: Not supported on FAPUs.
00/01
00: Disconnect; 01: Enable
Note: Not supported on FAPUs.
62
Remarks