FusionServer X6000 V6 Server
Technical White Paper
Item
Relative Humidity
(RH, Non-
Condensing)
Air volume
Operating
altitude
Corrosive air
pollutant
Particle pollutant
Issue 08 (2023-12-12)
Description
● Operating humidity: 8% to 90%
● Storage humidity (within three months): 8% to 85%
● Storage humidity (within six months): 8% to 80%
● Storage humidity (within one year): 20% to 75%
● Maximum humidity change rate: 20%/h
≥350 CFM
≤ 3050 m (10006.44 ft)
● If the server complies with ASHRAE Classes A1 and A2,
the maximum operating temperature decreases by 1°C
(1.8°F) for every increase of 300 m (984.25 ft) in altitude
above 900 m (2952.76 ft).
● When the server configuration complies with ASHRAE
Class A3 and the altitude is above 900 m (2952.76 ft), the
highest operating temperature decreases by 1°C (1.8°F) for
every increase of 175 m (574.14 ft).
● When the server configuration complies with ASHRAE
Class A4 and the altitude is above 900 m (2952.76 ft), the
highest operating temperature decreases by 1°C (1.8°F) for
every increase of 125 m (410.1 ft).
● HDDs cannot be used at an altitude of over 3,050 m
(10,006.44 ft).
Maximum corrosion product thickness growth rate:
● Copper corrosion rate test: 300 Å/month (meeting level G1
requirements of the ANSI/ISA-71.04-2013 standard on
gaseous corrosion)
● Silver corrosion rate test: 200 Å/month
● The equipment room environment meets the requirements
of ISO 14664-1 Class 8.
● There is no explosive, conductive, magnetic, or corrosive
dust in the equipment room.
NOTE
It is recommended that the particulate pollutants in the equipment room
be monitored by a professional organization.