Volume Report - Siemens FIREFINDER-XLS PMI Operation Manual

Table of Contents

Advertisement

PMI OPERATION MANUAL
Report - Volume
REPORT MODE
2-8
Pressing the "Select" button switches between percentage per foot and percentage
per meter. This feature applies to the DLC only.
This sensitivity report can then be printed by selecting the Print option if the system
has a report logging printer.
To view the Volume Report screen to see the amplifier and individual channel vol-
umes as played on that amplifier, press the Menu button on the PMI and select the
Report option by pressing the Report soft key. Press the More Info button on the
PMI to navigate to the specific submodule. Press the Status soft key to display all
possible Status Report types. Touch the Volume option to select it and the Volume
Report Screen appears. See Figure 2-9. The Volume Report shows the volume setting
at the selected amplifier and the volumes at which that amplifier will play individual
channels. (All menu items may not appear, depending on your configuration.)
Menu:Report:Status:Volume:View
PHY:FireFinder@1, DAC, ZAC-40@2

Volume Report

Amplifier Setting: 0 dB (Max)
CHANNEL
Audio Level (dB)
Emergency Page
0 (Max)
10:53
Category text information
Evac 1
0 (Max)
Evac 2
0 (Max)
Alert 1
0 (Max)
Alert 2
0 (Max)
Convenience Page
0 (Max)
Background Music
0 (Max)
Cancel
Print
Figure 2-9
Volume Report Screen
Each amplifier's volume and each channel's volume is set in Zeus. Non-emergency
channels can be modified at the LVM or SCM if they are configured for one of the
four available usages for volume adjustment (Selective Volume Up Convenience
Page, Selective Volume Down Convenience Page, Selective Volume Up Background
Music or Selective Volume Down Background Music).
To further illustrate how the Volume Report works, let's assume that the following
settings are in Zeus:
Amplifier Setting = -6dB
Evac 1 = 0dB
Alert 1 = 0dB
Convenience Page = -6dB
If a Volume Report is generated, the report will appear as follows (Figure 2-10):
Menu:Report:Status:Volume:View
PHY:FireFinder@1, DAC, ZAC-40@2
Volume Report
Amplifier Setting: -6dB
CHANNEL
Audio Level (dB)
Evac 1
-6
10:53
Category text information
Alert 1
-6
Convenience Page
-12
Cancel
Print
Figure 2-10
Volume Report
100%
GoTo
100%
GoTo
| CHAPTER 2