Voice Activations

Walktest Event Log

Walktest Reports

MAINTENANCE MODE
3-22
The volume for the Walktest channel is set low. During Walktest, speaker zones are
activated steady. The duration for each activation type is the same as for ZIC activation.
The tone specified for Walktest is File 1 Tone 1. The user may program a tone or
message to that tone location using the Zeus programming tool. Use caution when
selecting the tone or message. An inappropriate tone or message during a Walktest
might be disruptive.
A maximum of 5000 Walktest events will be stored in flash memory for reporting.
Walktest events are automatically stored. The storage cannot be disabled by the user.
Since a full walktest inspection of a system may be performed over a period of days,
weeks and/or months, the Walktest log remains in memory between individual
Walktest sessions. The Walktest log will also persist through database changes,
although not all data will be available for Walktest events from prior databases.
The user may manually erase the Walktest log at the PMI by selecting Report, Status,
Walktest, Clear Log.
Once the Clear Log soft key is pressed, the Walktest log is erased from memory and
cannot be recovered.
When the Walktest event log is full, the panel automatically erases the data. The
most recent 10% of the data is preserved in the new log. Since Walktest data will be
lost if the log is allowed to fill, the user is encouraged to extract the data, generate
reports, and clear the log before it fills. The capacity is intended to allow a full test of
all points on a system to be performed and logged.
Use the Walktest report feature to show which devices(s) have been tested. Using
the Report, Status, Walktest menu on the PMI, a report can be specified for a list of
all devices tested (complete log) or a list of all devices tested between a specified
time range.
Menu:Report:Status:Walktest
PHY:FireFinder@1, DLC@1
Walktest Report
SETTINGS:
Start Time:
Not Set
Stop Time :
Not Set
# Records :
45
Cancel
Settings
Clear Log
Figure 3-33
Walktest Report Screen
View