Normal mode is the absence of any off-normal conditions.
The screen displays SYSTEM STATUS: NORMAL with the time and date. If a custom
message has been programmed using the Zeus tool (refer to Zeus Quick Start Guide,
P/N 315-033875), the node custom message also displays in this mode. See Figure 1-6.
10:26:12 07/12/02
SYSTEM STATUS: NORMAL
CUSTOM MESSAGE
FireFinder - XLS System
Figure 1-6
Normal Mode Display
The POWER LED glows steady green in Normal mode when the System has AC
power. The ALARM, AUDIBLE ON, AUDIBLE SILENCE, SUPERVISORY, TROUBLE,
SECURITY (PMI-1/PMI-2), and PARTIAL SYSTEM DISABLE LEDs are off and the internal
audible is off.
Press the Menu button (see
See Figure 1-7 . The currently available options are described below.
Alert
Report
Menu
FireFighter@1
Press any lit green arrow key to continue.
10:53
Category text information
Press "?" for more help information.
ALERT: Firefighter's Mode, view events.
REPORT: View/Print event and system info.
MAINT: Control devices and inputs/outputs.
FUNCTION KEYS: Execute logic commands.
LOGOUT: Leave password protected area.
DIAGNOSTICS: For factory use only.
LAMP TEST: 30 second PMI LED test.
Logout
Diagnostics
Lamp Test
Figure 1-7
Menu Screen
When an event occurs in the system, the display enters the Alert or Firefighter's
mode automatically. The events are displayed in priority order, the local audible
sounds and the appropriate LED blinks. If the event caused notification appliances to
sound, the Audibles On indicator lights. At the bottom of the screen an Acknowledge
soft key is displayed. Pressing this key acknowledges the event and silences the local
audible. A Silence Audibles soft key is displayed at the bottom of the screen.
.
on page 1-2) to display a menu of all PMI options.
Maint
Function Keys
* The alternate language is only visible/present if the Zeus
Alt. Language*
programming tool has been set for two languages--a base
language and an alternate language.