Report Mode - Siemens FIREFINDER-XLS Installation, Operation And Maintenance Manual

Hide thumbs Also See for FIREFINDER-XLS:
Table of Contents

Advertisement

FIREFINDER-XLS INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Reset Procedures
Hard Reset
Soft Reset
REPORT MODE (Reporting Detector Sensitivities)
3-6
OPERATION
In addition, the System responds to troubles with other output functions (as pro-
grammed in the Zeus tool).
An Acknowledge Trouble soft key displays in the bottom left corner of the screen.
Press this key to acknowledge each trouble and to silence the local audible. The
blinking exclamation point (!) then changes to a check mark ()). See Figure 3-4.
If acknowledged troubles remain in the queue, the system will sound the local
audible every 24 hours as a reminder. A message will appear on the PMI and the
sounder will remain on until it is silenced.
There are two types of reset procedures that can be performed on the FireFinder-XLS
System: Hard Reset and Soft Reset.
Other terms for Hard Reset are Power-up, Initialization, and Cold Reset. Applying
power to the system performs a Hard Reset. Doing so initializes the entire system.
What Is Lost:
Alarm, supervisory, trouble, and security conditions (provided they have
returned to the normal state).
Arm/disarm.
Manual sensitivity adjustment.
What Is Not Lost:
Zeus program.
Time and date.
History log.
Time-based control.
A Soft Reset is performed by pressing the Reset System soft key. The system can
only be reset when all events (alarms, supervisories, securities and troubles) are
acknowledged and the notification appliances are silenced.
What Is Lost:
Alarm, supervisory, trouble, and security conditions (provided they have
returned to the normal state).
What Is Not Lost:
Any user entries such as time and date.
Arm/disarm.
Zeus program.
Manual sensitivity adjustment.
Time-based control.
Press the Menu button on the PMI (upper right) and select the Report option by
pressing the key with the lit green triangle pointing to the Report label.
Press the More Info/+ button on the PMI to navigate to the desired loop or specific
device. When More Info is pressed once it displays the FireFinder-XLS node.