Space-Ray ADU25 Installation And Operation Instruction Manual page 39

Overhead radiant tube heaters
Table of Contents

Advertisement

Place the compression coupling over the end of the tube.
a.
Use the small hole at the centerline of the coupling to check that the coupling is inserted correctly.
b.
Partially tighten the bolt nearest the end of the tube (approximately half closed).
c.
Fig. 23
Slide the next tube into the coupling.
d.
Make sure both tube ends are butted together.
e.
Finish tightening both bolts to 54-80 N·m torque to ensure a complete seal.
f.
Use the two self-drilling screws through the pre-punched holes to secure the tubes in the coupling.
g.
Fig. 23a
Check to ensure that the hardware is completely closed and the band is seated on the reaction block and
h.
interference pins as illustrated above.
Once all the heater body sections are attached, make sure that the heater system is level. If it is not, slight
i.
adjustments can be made using the turnbuckles. (See Section 7.0)
Fig. 23b
Important: NEVER reuse a coupling. Always install a new coupling only and
torque as per instructions above and the diagrams above.
-38-
Form #44201100
Oct 2019

Advertisement

Table of Contents
loading

Table of Contents