D6412/D4412

Terminal Quick Reference

15.0 Terminal Quick Reference
Silkscreen
Term
(below terminals)
1,2
18 VAC
3
Earth Ground Symbol
4
Data, Grn (Green)
5
Data, Yel (Y ellow)
6,7
Aux Power 12 VDC (-)
8,9
Aux Power 12 VDC (+)
JP3
Aux/Data (RYGB)
Red (Bat +)
Black (Bat -)
10
PO 4
11
PO 3
12
PO 2
13
Alrm +
14
PO 1, A
15
PO 1, B
16
L-1 (+)
L-1 (-)
18
Com
19
L-2
20
L-3
21
Com
22
L-4
23
L-5
24
Com
25
L-6
26
L-7
27
Com
28
L-8
29
T
30
T1
31
R1
32
R
JP2, PO1 Select æ
Auxiliary
Installer
45349D
18 V, 22 VA; up to 50 ft. (15.3 m), #18 AWG (1.2 mm), Stranded.
Earth Ground.
SDI data on Terminals 4 &5. Panel supports up to 1,000 ft. (305 m) of #22 AWG (0.8 mm) wire on these terminals (any
configuration).
Terminals 6-9 are Aux power. 600 mA. Include any programmable outputs (PO 1 to PO 4) not configured for alarm output.
PTC protected.
4-pin connector to Data bus and Aux power. Use to connect an installer keypad for keypad programming.
Battery (+) spade.
Battery (-) spade.
Programmable Output, up to 500 mA (-). Include in Aux Power calculations for all except 'Alarm' output functions. PTC
protected.
Programmable Output, up to 500 mA (-). Include in Aux Power calculations for all except 'Alarm' output functions. PTC
protected.
Programmable Output. 500 mA (-). Include in Aux Power calculations for all except 'Alarm' output functions. Supervised for
Horn/Speaker alarm function. PTC protected.
Alarm power. Up to 1,850 mA. PTC protected. Provides power for supervised siren driver (PO 2) and Alarm Output (PO 1).
Jumper sets PO 1 terminals A (14) and B (15) for 'dry' Form "A" contact or for Alarm Output.
Positive terminal of powered loop. Supports up to 15 smoke detectors (see the D6412/D4412 Smoke Compatibility List,
P/N: 46928). PTC protected.
Negative terminal of powered loop.
Common for Sensor Loop 2.
Sensor Loop 2 input. Wire length for Sensor Loops 2 to 8 are limited only by the resistance on the loop and potential EMI
problems. Resistance must be < 100 Ω with EOL resistor shorted and detection devices connected.
Sensor Loop 3 input.
Common for Sensor Loops 3 and 4.
Sensor Loop 4 input.
Sensor Loop 5 input.
Common for Sensor Loops 5 and 6.
Sensor Loop 6 input.
Sensor Loop 7 input.
Common for Sensor Loops 7 and 8.
Sensor Loop 8 input.
Tip of telephone line.
Tip of house (premises) phones.
Ring of house (premises) phones.
Ring of telephone line.
Configures PO 1 for Form "A" relay or Alarm Output.
Auxiliary Module and/or Programming Key Header.
Installer Jumper. Jumper required for keypad programming.
D6412/D4412 Installation Guide
Description
Page 64
© 2002 Radionics