Appendix A: Approved Applications Compliance Guide; Listings And Approvals - Bosch radlonlcs D6412 Installation Manual

Control/communicator
Hide thumbs Also See for radlonlcs D6412:
Table of Contents

Advertisement

Appendix A: Approved Applications Compliance Guide

Listings and Approvals

Fire
• UL
• CSFM
• NYC-MEA - Approved by New York City's Materials and Equipment Acceptance System.
Burglary
• UL
• SIA
Introduction
The System Chart references components evaluated and listed by Underwriters' Laboratories for compatibility
with the Control/Communicator. These components meet the basic system requirements for the applicable
standard.
The System Wiring Diagram, Issue A shows the relationship between the panel and the accessory components
referred to in the System Chart.
Optional Compatible Equipment
You can use UL listed components that do not require evaluation for electrical compatibility in many applications
when installed according to the manufacturer's instructions.
Burglary Applications
You can use UL listed burglary alarm sensors that do not require evaluation for electrical compatibility in
burglary applications. In some cases you must use a UL listed Radionics interface module in conjunction with
the sensors. Consult the individual component specification and installation documents to determine suitability.
Test weekly: UL Standard 1023 requires a weekly test for residential burglary applications.
Auto Arming for Bank Safe/Vault Applications (UL 609)
To auto-arm for Bank Safe/Vault applications, use an Auto On/Auto Off Sked (schedule). Set the Auto On Sked
to arm the system on a 7 day (1 week) timer no later than 10 p.m.. Set the Auto Off Sked to disarm the system
no sooner than 6 a.m. the next business day. Adjust these skeds so that the system is armed during non-
business hours (such as holidays and weekends). These times may be adjusted if they conflict with normal
business hours and/or any non-business hour carry-over (extended holiday/closed periods). See Skeds in the
D6412/D4412 Program Entry Guide (P/N: 45351) for Sked set-up instructions.
Fire Applications
You can use UL listed fire initiating devices not requiring electrical compatibility evaluation in any application.
For example: 4-wire smoke detectors, heat detectors, water flow switches, and manual pull stations are suitable
fire initiating devices. Consult the individual component specification and installation documents to determine
suitability.
Two-wire smoke detectors only connect to the panel on the sensor loop for location 1. Two-wire detectors must
be evaluated for electrical compatibility, and must be UL listed for use with the panel. See the Radionics
Technogram Smoke Detectors Compatible with the D6412/D4412 (P/N: 46928), or you may contact the detector
manufacturer.
When using 4-wire smoke detectors, install a suitable power supervision unit according to the manufacturer's
instructions. Use the D130 Relay Module, DX3010 Octo-Output, or PO 1 to provide reset capability. See the
Outputs section of this manual for details on the installation of the DX3010.
For battery calculations, refer to Current Rating Chart for Standby Battery Calculations, Standby Battery
Requirements, and Standby Battery Calculation for NFPA 72 Fire Alarm Applications.
© 2002 Radionics
D6412/D4412 Installation Guide
Page 67
D6412/D4412
Appendix A
45349D