D6412/D4412
Off-board Sensor Loops
8.2

DX2010 Point Expander Module

8.2.1

DX2010 Overview

You can connect up to five DX2010 Point Expander Modules to the D6412 (three to the D4412). In the single
point configuration, each DX2010 adds eight points to the system. In the doubled point configuration, each
DX2010 adds 16 points to the system. Table 5 shows how the DX2010 Point Expander sensor loops are
assigned to point locations.
• Current Draw without Aux Output Terminals: 35 mA Standby
• Current Draw with Aux Output Terminals: 135 mA maximum with connected accessories
Review the Power Outputs section of this manual to be sure you provide enough power for the Point Expander
Modules and any other powered devices you connect to the panel.
Refer to the DX2010 Installation Guide (P/N: 46413) for complete installation, addressing and operating
instructions.
8.2.2

DX2010 Installation

Failure to follow the mounting instructions in this manual may result in damage to the module.
WARNING
The DX2010 contains static-sensitive components and must be handled with care. Follow anti-static procedures
when handling the modules.
The DX2010 module can be mounted in a D203 Enclosure. Mount the module in the enclosure as shown in
Figure 14.
You can also install the DX2010 board in the control panel's enclosure. The D2203 enclosure can hold up to five
DX2010 modules (see Figures 15 and 16).
45349D

Figure 14: Installing the DX2010 in D203 Enclosure

D6412/D4412 Installation Guide