Off-board Outputs

Unexpected Output at PO 1 to PO 4: If these outputs do not provide the alarm output you expect:
• Check the programming for Programmable Outputs in the Outputs section of the D6412/D4412 Program Entry
Guide (P/N: 45351).
• Check the Point Index Configuration section of the D6412/D4412 Program Entry Guide to verify the points you
are activating are programmed for alarm output.
If Programmable Output 2 is configured as a supervised siren driver (in combination with the Alrm +
terminal), you must connect a 4 Ω Ω or 8 Ω Ω siren/speaker to PO 2 to clear the siren/speaker supervision
trouble.
IMPORTANT
10.0 Off-Board Outputs

10.1 Overview

You can expand the total number of programmable outputs to 20 for the D6412 (12 for the D4412) using the
DX3010 Octo-Output Module (two required for 20 outputs) or DX3020 Module. Instructions for the DX3010
Module are included in this manual (as well as with the module). The DX3020 Module emulates two DX3010
Modules with the D6412 (emulates one with the D4412). DX3020 specific instructions are included with the
module.

10.2 DX3010 Octo-Output Module

10.2.1 Overview
The DX3010 Octo-Output Module allows you to add outputs to your system in groups of eight. You can add up to
two DX3010 Octo-Output Modules to the D6412 (one to the D4412). Combining the four on-board
programmable outputs with two DX3010 Octo-Output Modules (one on the D4412) makes a total of 20
programmable outputs available for the D6412 (12 for the D4412). Review Section 5.0, Power Outputs, to be
sure you provide enough power for the Octo-Output Modules and any other powered devices you connect to the
panel.
You can assign any of the programmable output functions to the Octo-Output Module's individual outputs
separately. See Outputs in the D6412/D4412 Program Entry Guide (P/N: 45351) for programming details.
The DX3010 relay outputs are not supervised and cannot be used in fire or combined fire/burglary
installations for primary indicating devices.
IMPORTANT
Current Draw: 10 mA Standby plus 40 mA for each energized output (relay) for a total of 330 mA maximum with
all eight outputs energized.
Refer to the DX3010 Installation Guide (P/N: 46925) for complete installation, addressing and operating
instructions.

10.2.2 Configuring the DX3010 Octo-Output Module

Outputs may activate when setting the DX3010's switches, programming the panel, resetting the panel
or applying power to the panel. You may wish to disconnect equipment connected to outputs while
performing these functions.
WARNING

10.2.3 Relay Outputs

Each DX3010 output provides a Form "C" dry contact rated for 5.0 A at 28 VDC. Normally-open, common, and
normally-closed terminals are available for each relay output. When an individual output is activated, there is
continuity between the normally-open and common terminals. When the output is not activated, there is
continuity between the normally-closed and common terminals.