Installing The Assembly; Connecting Earth Ground; Figure 2: Enclosure Mounting - Bosch radlonlcs D6412 Installation Manual

Control/communicator
Hide thumbs Also See for radlonlcs D6412:
Table of Contents

Advertisement

3.5

Installing the Assembly

1)
Place the panel mounting clips on the appropriate standoff in the enclosure (see Figure 2).
2)
Slide the panel into the slots at the top of the enclosure and then secure it with the two screws provided
(see Figure 2).
Connect earth ground to the panel before making any other connections (see Section 3.5.1, Connecting
3)
Earth Ground).
Mounting Slots
3.5.1

Connecting Earth Ground

To help prevent damage from electrostatic charges or other transient electrical surges, connect the system to
earth ground before making any other connections. A grounding rod or cold water pipe are recommended earth
ground references.
Do not use telephone or electrical ground for the earth ground connection. Use 14-16 AWG (1.8 to 1.5
mm) wire when making the connection. Use only the earth ground terminal. Do not connect any other panel
terminals to earth ground.
© 2002 Radionics
D6412/D4412 PCB Location
D6412/D4412 BOARD
TERMINALS

Figure 2: Enclosure Mounting

D6412/D4412 Installation Guide
Page 17
D6412/D4412
Installation
Install the PCB support standoffs here (P/N: 30503B)
Corner of
D6412/D4412
Mounting
Enclosure
PCB
Clip
Standoff
Mounting Clip Assembly
=
45349D