FPT-DACT | Operation & Installation Guide | 3.0 System Startup
3.0

System Startup

3.1

System Power up

This section describes the proper sequence of events
when first powering up the FPT-DACT.
3.1. 1

Before Power Up

Before applying power to the FPT-DACT, verify:
All wiring connections are made according to
Section 2.2 Connecting the FPT-DACT on page 12).
All connectors are firmly seated onto their
appropriate
headers. Refer to Section 2.2 Connecting
the
FPT-DACT).
Input power requirements comply with the power
specifications in Table 1 on page 5. The power
supplied to the FPT-DACT from the FACP is not
shorted and meets the necessary power requirements
for the FPT-DACT.
All telephone line connections are made according
to Figure 13 on page 15.
Both RJ31X male connectors are firmly seated in the
RJ31X female connectors located on the FPT-DACT
board.
All input points are properly terminated with the
supplied 2.2 kΩ EOL resistors for supervised
operation.
The trouble relay connections are made according to
Figures 11 and 12 on pages 14 and 15.
3. 1 .2

After Power Up

After power is applied to the FPT-DACT, verify the
following conditions occur:
All LEDs light briefly and the trouble relay toggles.
The System Trouble LED lights.
The Heartbeat LED flashes indicating the FPT-
DACT is functional.
3.2

System Quick Start

The FPT-DACT starts in a trouble condition until the
following steps are taken:
1.
Connect the FMR-DACT-KEYPAD. Refer to
Connecting the Keypad to the FPT-DACT in Section
2.2.3 Telephone Connections on page 16.
2. Program the FPT-DACT using the FMR-DACT-
KEYPAD. Refer to Section 5.1 Using the Keypad on
page 28.
3. Configure the five input points. Refer to
1: CONFIGURE in Section 5.0 Programming
beginning on page 28.
4. Assign the FPT-DACT account numbers. Refer to
1: ACCOUNT NUMS in Section 5.0 Programming.
1/05 | F01U002505B
5. Assign the FPT-DACT telephone numbers. Refer to
2: PHONE NUMS in Section 5.0 Programming.
When you complete Steps 1 through 5, refer to
Section 5.0 Programming
to complete the programming
sequence.
If the FPT-DACT is correctly programmed
and input wiring is properly connected and
supervised, only the Heartbeat LED flashes.
This indicates normal system operation.
Verify the correct communications by
performing a Manual Communications Test.
Refer to 1: TEST COMM in Section 5.5.4,
3-TEST on page 44 for testing instructions.
Test according to NFPA 72 Chapter
10.4.1.2 (2002) following any modifications,
repairs, upgrades, or adjustments to the
system.
Refer to Appendix A on page 45 for
information on error messages or messages
indicating abnormal operating conditions.