If you need to power the DX3010 from an external power source, connect it to the power source and the panel
as shown in Figure 30. See Section 4.3, External Power Supply, for external power supply restrictions.
10.2.6 Address Programming
Each DX3010 module connected to the panel must have its address jumpers set to the address shown in Table
12.
Any time the address jumpers are changed, you must cycle the control panel power OFF and then ON for the
changes to take effect. Set the address jumpers as shown in the Table 13. "DN" indicates that the DIP switch is
CLOSED (Down). See Figure 31 for DIP Switch configuration.
Module Address 150
© 2002 Radionics
DX3010
Y
Yellow
Green
G
B
Black
R
+
External 12 VDC
Power Supply
NC
C
NO
8
Figure 30: Wiring for External Power Supply
Panel
D6412/D4412
D6412 only
Table 12: DX3010 Address Settings
SDI
Panel
Address
D6412/D4412
150
D6412 only
151
Table 13: DX3010 Address Jumper Settings
Example:
1 2 3 4 5 6
Figure 31: DX3010 Address DIP Switches
D6412/D4412 Installation Guide
D6412/D4412
Green
Yellow
Black
R
Y
-
G
B
Output #
SDI Address
5 to 12
SDI Address 150
13 to 20
SDI Address 151
DIP Switch, X=DIP Switch is CLOSED
1
2
4
8
16
UP
UP
UP
UP
UP
DN
UP
UP
UP
UP
OPEN
=Switch OPEN (Up)
=Switch CLOSED (Down)