3.2 Mapping Modbus Holding Registers

A Modbus holding register is a bit binary data item which can be both read and written.
Registers can be mapped to a specific parameter by using the customization feature in MyDrive® Insight.
The first 19 holding registers are pre-mapped or reserved and cannot be changed. From location 20 onwards, registers can be map-
ped freely.
The parameter mapped to 1 register can be re-mapped to another register.
Table 14: Modbus Holding Registers
Location
Reference Type
1
Parameter
2
Parameter
3
Parameter
4
Parameter
5
Parameter
6
Parameter
7
Parameter
8
Parameter
9
Parameter
10
Parameter
11
Parameter
12
Parameter
13
Parameter
14
Parameter
15
Parameter
16
Parameter
17
Parameter
18
Parameter
19
Parameter
20
...
...
...
1.
In MyDrive
Insight, go to Customization → Live → MODBUS → Holding Registers.
®
-
a.
To add a single register, click the + Add Item icon.
-
Danfoss A/S © 2023.09
N O T I C E
Reference (parameter number)
Fieldbus profile (1301)
Fieldbus Control Word (1335)
Fieldbus Main Reference (1339)
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Fieldbus Status Word (1307)
Fieldbus Main Actual Value (1308)
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
...
...
Modbus Data Mapping