Danfoss iC7 Series Operating Manual page 33

Hide thumbs Also See for iC7 Series:
Table of Contents

Advertisement

iC7 Series Modbus
Operating Guide
1.
Configure IPv4 settings.
-
In MyDrive
Insight, go to Setup and Service → Interface configuration → Interface X1/X2 → IPv4 settings.
®
-
In the control panel, navigate to parameter group 10.2 Communication Interfaces.
Table 23: IPv4 Settings
Function
Interface X1/X2
MAC address
IPv4 addressing
method
Requested IPv4 ad-
dress
Requested IPv4
subnet mask
Requested IPv4
gateway address
Enable ACD
DNS server 1, 2
Table 24: Ethernet Port Configuration (X1/X2)
Menu Index
Function
10.2.5.2.5
Link configuration
10.2.6.2.5
Danfoss A/S © 2023.09
Value
Description
00:1B:08:xx:xx:xx
The MAC address of interface X1/X2. The value is read-only.
Disable
Only link-local IP address in the 169.254.xxx.xxx range is active.
Static IP
A static IP address is entered manually.
Automatic
IP address is assigned via a DHCP or BOOTP server.
xxx.xxx.xxx.xxx
If Automatic is selected as the IPv4 addressing method and no DHCP/
BOOTP server is present, the X1/X2 interface automatically configures an
IP address and subnet mask in the 169.254.xxx.xxx range.
xxx.xxx.xxx.xxx
The requested IPv4 subnet mask for the interface.
xxx.xxx.xxx.xxx
Requested IPv4 gateway address for the interface.
Enable/disable (de-
Request to enable or disable Address Conflict Detection for the interface.
fault)
The change will not take effect before a power cycle is performed. If no
conflicts are detected, ACD activity displays 0. If an address conflict oc-
curs, the ACD activity displays 1, and the IPv4 interface will revert to an
automatically assigned IP address in the 169.254.xxx.xxx range.
xxx.xxx.xxx.xxx
The user-requested Domain Name Server 1 for the interface (for manual
IP addressing mode only).
Value
-
AutoNeg
-
10 MbpsFullDuplex
-
10 MbpsHalfDuplex
-
100 MbpsFullDuplex
-
100 MbpsHalfDuplex
Modbus Configuration
Description
Configures the Ethernet link parameter.
AQ456329149698en-000101 / 136R0334 | 33