5.6 Configuring Modbus Data Settings

Use MyDrive® Insight or the control panel to select persistent storage and the byte and word order for Modbus communication.
1.
Using MyDrive
Insight or the control panel, navigate to parameter 10.3.3.2.
®
Table 25: Parameters for Modbus Data Settings
Menu in-
Parameter
dex
name
10.3.3.2.1
Persistent
Storage
10.3.3.2.3
Byte Order
10.3.3.2.4
Word Order
36 | Danfoss A/S © 2023.09
Value
Description
Persistent Storage enables storing parameters written via
-
Disable
Modbus in non-volatile memory.
-
Enable
Byte order of holding register.
-
Little Endian
-
Big Endian (default)
Word order when mapping parameters (for example, 32-bit
-
Little Endian (default)
REAL) in multiple registers.
-
Big Endian
N O T I C E
Enabling Persistent Storage causes a decrease in Modbus
communication performance.
AQ456329149698en-000101 / 136R0334