Ic Dc/Dc Converter Profile; Control Word (Ctw) In Ic Dc/Dc Converter - Danfoss iC7 Series Operating Manual

Hide thumbs Also See for iC7 Series:
Table of Contents

Advertisement

iC7 Series Modbus
Operating Guide

2.2.4 iC DC/DC Converter Profile

2.2.4.1 Control Word (CTW) in iC DC/DC Converter

Table 11: Fieldbus Control Word
Bit
Name
Description
0
Switch On Enable
0: Running is prevented or interrupted
1: Running is not prevented or interrupted
1
--
Reserved
2
Quick Stop In-
0: Initiate quick stop
verse
1: No action
3
Start
0: Stop modulation if the unit is running
1: Start modulation or keep the unit running
4
--
Reserved
5
--
Reserved
6
--
Reserved
7
Fault Reset
0: No action
1: Reset active faults and other events
8
--
Reserved
9
--
Reserved
10
Data Valid
0: Ignore the current incoming process data values, instead use the last
processed value when the Data Valid bit was true.
1: Use the current incoming process data values
11
Watchdog
Incoming fieldbus Watchdog bit
12
Vendor Specific
0: Deactivate the vendor-specific function using digital input/output virtual
Bit 1
slot 6412
1: Activate the vendor-specific function using digital input/output virtual
slot 6412
13
Vendor Specific
0: Deactivate the vendor-specific function using digital input/output virtual
Bit 2
slot 6413
1: Activate the vendor-specific function using digital input/output virtual
slot 6413
14
Vendor Specific
0: Deactivate the vendor-specific function using digital input/output virtual
Bit 3
slot 6414
1: Activate the vendor-specific function using digital input/output virtual
slot 6414
15
Vendor Specific
0: Deactivate the vendor-specific function using digital input/output virtual
Bit 4
slot 6415
Danfoss A/S © 2023.09
Further Information
Depending on parame-
ter 5114, a rising edge is
or is not required for the
unit to start modulation.
Edge sensitive - a reset
command is issued
when a rising edge is de-
tected.
In Modbus protocol, the
incoming process data
refers to the control
word only, excluding bit
11 Watchdog.