Bit
Name
Description
1: Activate the vendor-specific function using digital input/output virtual
slot 6415

2.2.4.2 Status Word (STW) in iC DC/DC Converter

Table 12: Fieldbus Status Word
Bit
Name
Description
0
Ready to Switch
0: Not ready to switch on
On
1: Ready to switch on
1
Converter Ready
0: The converter is not ready to start (Check the DC/DC Ctrl. Ready
Status Word)
1: The converter is ready to start modulating, if Ready to Switch
On is true and all the start and run interlocks are present
2
Running
0: The unit is not running (modulating)
1: The unit is running (modulating)
3
Fault
0: No faults active
1: One or more faults are active
4
--
Reserved
5
Quick Stop In-
0: Quick stop active
verse
1: Quick stop not active
6
--
Reserved
7
Warning
0: No warnings active
1: One or more warnings are active
8
--
Reserved
9
Control by PLC
0: The active control place is not fieldbus
1: The active control place is fieldbus
10
--
Reserved
11
Run Enabled
0: Run enable from the dedicated input signal is missing
1: Run enable from the dedicated input signal is present
12
--
Reserved
13
--
Reserved
14
--
Reserved
15
Watchdog
Outgoing fieldbus watchdog bit

2.3 Network Topologies

Communication interface X1/X2 is used for fieldbus connection.
18 | Danfoss A/S © 2023.09
Overview
Further Information
Additional Information
This bit is true if all following con-
ditions are satisfied:
Switch on enable is present.
Quick stop is not requested.
No faults are active.
AQ456329149698en-000101 / 136R0334