iC7 Series Modbus
Operating Guide
b.
To map multiple registers, click the – Add Multiple Items icon.
Table 15: Holding Register Settings
Column
Description
Location
Refers to the register number. Registers are mapped from address 40000–4FFFF.
Reference
-
type
-
-
-
-
Reference
The name of the mapped parameter, feature, or event. Value for Constant type.
Source type
Data type of mapped parameter
Index
Index pointer for array parameters
Length
Number of bytes for string-type parameters.
Register type
Data type of the mapped parameter
By default, the Customizer selects a register type that matches the data type of the selected parame-
ter.
Scaling
Scales the parameter value on the Modbus interface by dividing it by the scaling value entered.
Unit
Unit of the mapped parameter
Permissions
Setting Read/Write permissions for each register
Watchdog
-
-
Example
Mapping parameter of the REAL 32-bit datatype results in 2 consecutive register mappings.
Table 16: Example of a Holding Register Mapping
Location
Reference Type
20
Parameter
22
Parameter
24
...
Events from the device event log can be mapped into holding registers, starting from the most recent event.
Each Event results in six consecutive register mappings.
Table 17: Example of an Event Register Mapping
Register
Description
n
Timestamp
n+1
24 | Danfoss A/S © 2023.09
Terminal: Mapping a terminal on an option to a register.
Parameter: Mapping a parameter to a register.
Constant: Mapping a constant value to a register.
Feature: Mapping a register to a feature, for example, Factory restore.
Event: Mapping events to registers.
Watchdog1: Process data timeout watchdog
Timeout time is configured in parameter 10.3.1.6 Process Data Timeout Time.
The Watchdog timer is triggered when writing to the mapped coil or register.
Watchdog2: Not used
Reference (parameter number)
Motor Current (9000)
Heat Sink Temperature (2950)
...
Format
Seconds/milliseconds [SS.SSS]
Hours/Minutes [HHMM]
Source Type
Register Type
REAL
Two Consecutive Floating point
REAL
Two Consecutive Floating point
...
...
(1)
(1)
AQ456329149698en-000101 / 136R0334
Modbus Data Mapping