Mitsubishi Heavy Industries VRF with KNX, Serial and IP support
5.2.4. Connection Procedure for KNX
Connect the KNX TP communication cable to the gateway's KNX port.
IMPORTANT
Observe polarity.
NOTE
See the
Wiring diagram (page
5.2.5. Connection Procedure for BACnet
For BACnet/IP:
Connect the BACnet/IP Ethernet cable to the gateway's Ethernet Port. The correct cable to use depends on
where the gateway is connected:
• Connecting directly to a BACnet/IP device: use a crossover Ethernet UTP/FTP CAT5 or higher cable.
• Connecting to a hub or switch of the LAN of the building: use a straight Ethernet UTP/FTP CAT5 or higher
cable.
NOTE
Some devices detect the difference automatically and adjust themselves.
NOTE
When commissioning the gateway for the first time, DHCP will be enabled for 30 seconds. During
that time, if there is a DHCP server, an IP address will be automatically assigned to the gateway. If
there is no DHCP, you can type an IP address of your choice. After that time, the default IP address
192.168.100.246 will be automatically set.
IMPORTANT
If communicating through the LAN of the building, contact the network administrator and make sure
traffic on the used port is allowed through all LAN paths.
For BACnet MS/TP:
Connect the BACnet MS/TP communication cable to the gateway's EIA-485 port.
IMPORTANT
Observe polarity.
Page 14 of 36
10).
Connection
USER MANUAL Version 1.2.7