HMS Networks Intesis IN776MHI00 O000 Series User Manual page 30

Mitsubishi heavy industries vrf with knx, serial and ip support
Hide thumbs Also See for Intesis IN776MHI00 O000 Series:
Table of Contents

Advertisement

Integration into KNX Systems
Description
Control_Operation mode
Status_Operation mode
Control_Mode Cool/Heat
Status_Mode Cool/Heat
Control_Auto mode
Status_Auto mode
Control_Heat mode
Status_Heat mode
Control_Cool mode
Status_Cool mode
Control_Fan mode
Status_Fan mode
Control_Dry mode
Status_Dry mode
Control_Temperature setpoint
Status_Temperature setpoint
Control_Fan speed enumerated
Status_Fan speed enumerated
Control_Fan speed scaling
USER MANUAL Version 1.2.7
Mitsubishi Heavy Industries VRF with KNX, Serial and IP support
Function
0: Auto
1: Heat
2: Dry
3: Fan
4: Cool
0: Auto
1: Heat
2: Dry
3: Fan
4: Cool
0: Cool
1: Heat
0: Cool
1: Heat
1: Set auto mode
1: Auto mode active
0: Auto mode not active
1: Set heat mode
1: Heat mode active
0: Heat mode not active
1: Set cool mode
1: Cool mode active
0: Cool mode not active
1: Set fan mode
1: Fan mode active
0: Fan mode not active
1: Set dry mode
1: Dry mode active
0: Dry mode not active
Celsius: 16 .. 30°C
Fahrenheit: 60 .. 86°F
Celsius: 16 .. 30°C
Fahrenheit: 60 .. 86°F
0: Low
1: Medium
2: High
3: Powerful
0: Low
1: Medium
2: High
3: Powerful
Thresholds:
0 .. 24%
25 .. 49%
50 .. 74%
75 .. 100%
DPT
5.x (1byte)
5.x (1byte)
1.100-DPT_Heat/Cool (1bit)
1.100-DPT_Heat/Cool (1bit)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
9.001/9.027-DPT_Value_Temp (2byte)
9.001/9.027-DPT_Value_Temp (2byte)
5.x (1byte)
5.x (1byte)
5.001-DPT_Scaling (1byte)
Flags
Ri, W, U
R, T
Ri, W, U
R, T
Ri, W, U
R, T
Ri, W, U
R, T
Ri, W, U
R, T
Ri, W, U
R, T
Ri, W, U
R, T
Ri, W, U
R, T
Ri, W, U
R, T
Ri, W, U
Page 27 of 36