Mitsubishi Heavy Industries VRF with KNX, Serial and IP support
Table 6. Outdoor units
Description
Status_OU Compressor 1 Frequency
Status_OU Compressor 2 Frequency
Status_OU Heat Exchange low 1 temperature
Status_OU Heat Exchange low 2 temperature
Status_OU Heat Exchange low 3 temperature
Status_OU Heat Exchange low 4 temperature
Status_OU Heat Exchange high 1 temperature
Status_OU Heat Exchange high 2 temperature
Status_OU Heat Exchange high 3 temperature
Status_OU Heat Exchange high 4 temperature
Status_OU Unit temperature
Status_OU Discharge pipe temperature 1
Status_OU Discharge pipe temperature 2
Status_OU Crankcase temperature 1
Status_OU Crankcase temperature 2
Status_OU Compressor current 1
Status_OU Compressor current 2
Status_OU High pressure
Status_OU Low pressure
Table 7. Indoor units
Description
Status_CommError
Control_On/Off
Status_On/Off
Control_Operation mode
Status_Operation mode
Page 26 of 36
Function
Hz
14.033-DPT_Value_Frequency (4byte)
Hz
14.033-DPT_Value_Frequency (4byte)
°C / °F
9.001/9.027-DPT_Value_Temp (2byte)
°C / °F
9.001/9.027-DPT_Value_Temp (2byte)
°C / °F
9.001/9.027-DPT_Value_Temp (2byte)
°C / °F
9.001/9.027-DPT_Value_Temp (2byte)
°C / °F
9.001/9.027-DPT_Value_Temp (2byte)
°C / °F
9.001/9.027-DPT_Value_Temp (2byte)
°C / °F
9.001/9.027-DPT_Value_Temp (2byte)
°C / °F
9.001/9.027-DPT_Value_Temp (2byte)
°C / °F
9.001/9.027-DPT_Value_Temp (2byte)
°C / °F
9.001/9.027-DPT_Value_Temp (2byte)
°C / °F
9.001/9.027-DPT_Value_Temp (2byte)
°C / °F
9.001/9.027-DPT_Value_Temp (2byte)
°C / °F
9.001/9.027-DPT_Value_Temp (2byte)
Amperes
14.019-DPT_Value_Electric_Current (4byte)
Amperes
14.019-DPT_Value_Electric_Current (4byte)
MPa
14.058-DPT_Value_Pressure (4byte)
MPa
14.058-DPT_Value_Pressure (4byte)
Function
0: No error 1: Error
0: Off 1: On
0: Off 1: On
0: Auto
1: Heat
3: Cool
9: Fan
14: Dry
0: Auto
1: Heat
3: Cool
9: Fan
14: Dry
Integration into KNX Systems
DPT
DPT
1.005-DPT_Alarm (1bit)
1.001-DPT_Switch (1bit)
1.001-DPT_Switch (1bit)
20.105-DPT_HVACContrMode (1byte)
20.105-DPT_HVACContrMode (1byte)
USER MANUAL Version 1.2.7
Flags
R, T
R, T
R, T
R, T
R, T
R, T
R, T
R, T
R, T
R, T
R, T
R, T
R, T
R, T
R, T
R, T
R, T
R, T
R, T
Flags
R, T
Ri, W, U
R, T
Ri, W, U
R, T