Table A.2- Ambient Conditions - Reliance electric GV3000 Instruction Manual

A-c power modules
Hide thumbs Also See for GV3000:
Table of Contents

Advertisement

Appendix A
Technical Specifications
Table A.1 - Service Conditions
A-C Line Distribution System Capacity (maximum)
1000KVA, three-phase with 25,000 amps symmetrical
for 460 VAC Units
fault current capacity with a line impedanceof less
than 8%
Control Method
All-digital vector, sinusoidal pulse-width-modulated
(PWM)
Displacement Power Factor
0.96
Line Frequency
50/60Hz (+2 Hz)
Line Voltage Variation
— 10% to +10%
Line Dip Ride Through
Maximum 500 milliseconds - vector
Adjustable up to 999.9 seconds (See R042) - V/Hz
Motor Lead Lengths
76 meters (250 feet) total
Analog Speed Reference Accuracy
0.5%
Acceleration Adjustment Range
0.1 to 999.9 seconds (within the ability of current)
Carrier Frequency
2 Hz, 4 Hz, or 8 Hz, software-selectable
Current Limit Adjustment
U.006 to 150% (based on drive nameplate rating)-
vector
50% to 110% (based on drive nameplate rating) - V/Hz
Service Factor
1.0
Speed Adjustable Range
From 0 RPM to maximum speed
Speed Regulation
Vector - 0.01% long term steady state
V/Hz - motor slip dependent
Speed Reference Resolution
1 RPM with local keypad, —4095 to +4095 counts with
a networkor serial reference
Torque Control Response
180 to 220 Hz
Torque Linearity
+3% with optimal parameter setting (typical) (see
parameter U.005)
Table A.2 - Ambient Conditions
Condition
Specification
Operating Temperature (Ambient)
0° to +40° C (32° to 104°F)
Storage Temperature (Ambient)
—40° to +65°C (—40° to +149°F)
Humidity
5 to 95% (non-condensing)