Reliance electric GV3000 Instruction Manual page 63

A-c power modules
Hide thumbs Also See for GV3000:
Table of Contents

Advertisement

Table 7.1 - Wiring Signal and Control I/O to the Terminal Strip (Continued)
Terminal
Number
Description
Parameters/Wiring Connections
Wiring the ResetInput
22
Digital Input 3
The following parameter must be set:
(Reset)
P.000: Control Source
16
ec
RESET
Terminal 22 On = Reset
Wiring the Stop/Start Inputs
23
Digital Input 2
The following parameter must be set:
(Stop)
24
Digital Input1
P.000: Control Source
(Start)
P.025: Stop Type
16
23
16
24
STOP
START
_|-
olo
Terminal 23 Off = Stop
Terminal 24 On Transition = Start
25
24 VDCIsolated Common
Wiring the Snubber Resistor
26
Snubber Resistor Braking
Used with Snubber Resistor Braking Kit M/N 2DB4010.
Control Signal
Refer to the kit's instruction manual for installation
instructions.
27
+24 VDC Isolated Common
7-14