Table 7.1 - Wiring Signal and Control I/O to the Terminal Strip (Continued)
Terminal
Number
Description
Parameters/Wiring Connections
Wiring a Function Loss Input
20
Digital Input 5
(Function Loss)
The following parameters mustbeset:
P026: Function Loss Response
A signal must be present at terminal 20 for the drive to be
able to start. See figures 7.1 and 7.2. The drive is shipped
from the factory with a jumper between terminals 16 and 20
which provides the signal. The function loss input should
be in series with the drive's external interlocks. In this case,
the jumper must be removed before the connections are
made. See figure 2.12.
TERMINAL STRIP
161718192021
16171819 2021
COOGON
|WOOLOOY
KT
baeoipel
SAFETY INTERLOCKS
REMOVE FACTORY FUNCTION
CONNBUSS
LOSS JUMPER HERE
PUSHBUTTON
(or from 16A and 20A on 15-60HP drives)
Terminal 20 On = No Function Loss
Wiring a Run/Jog Input
21
Digital Input 4
(Run/Jog)
The following parameters mustbeset:
P.000: Control Source
P020: Jog Speed Reference
P021: Jog Ramp Accel Time
P022: Jog Ramp Decel Time
16
el
RUN
JOG
Terminal 21 On = Jog Operation
7-13