Advertisement

Table 7.1 - Wiring Signal and Control I/O to the Terminal Strip (Continued)
Terminal
Number
Description
Parameters/Wiring Connections
Wiring a Remote/Local Input
16
+24 VDC Power Supply
Currentlimited for remote input logic use only.
17
Digital Input 8
Digital input 8 is control function programmable through
(Default - Remote/Local)
parameter P.007.
WARNING
IF A MAINTAINED START CONTACT IS USED WHEN THE CONTROL SOURCE = rE,
SWITCHING FROM LOCAL TO REMOTE FROM THE TERMINAL STRIP WILL CAUSE POWER
TO BE APPLIED TO THE MOTOR IF THE REMOTESTART CONTACTIS CLOSED. STAY CLEAR
OF ROTATING MACHINERYIN THIS CASE. FAILURE TO OBSERVE THIS PRECAUTION COULD
RESULT IN BODILY INJURY.
The following parameters mustbeset:
P000: Control Source
(Only active when P000 = rE)
P006: Second Menu Password
P007: Terminal Strip Digital Inputs Configure (Selects
and assigns a control function to digital inputs
6 to 8).
P008: Terminal Strip Speed Reference Source
(Analog, Motor Operated Potentiometer (MOP), or
Preset Speeds)
Note that based on the settings of parameters P.000, P007,
P008, and 1.030 if an RMI board is used, the following
parameters can affect digital input 8.
P.023: MOP Accel/Decel Time
P024: MOP Reset Configuration
P031 to R038: Preset Speeds 1-8
Refer to the GV3000 Programming instruction manual
(D2-3339) for additional information.
16
17
REMOTE
LOCAL
Terminal 17 On = Local Control
Diagram showsfactory setting.
7-10