Verifying Power Module Input Ratings Match Supplied Power; Wiring Requirements For The Drive; Meeting Terminal Strip Input And Output Specifications; Determining Wire Size Requirements - Reliance electric GV3000 Instruction Manual

A-c power modules
Hide thumbs Also See for GV3000:
Table of Contents

Advertisement

3.1.4 Verifying Power Module Input Ratings Match Supplied Power
It is important to verify that plant power will meet the input power requirements of the GV3000 drive's
Power Module circuitry. Refer to table 2.1 for input power rating specifications. Be sure input power to
the drive correspondsto the drive nameplate voltage and frequency.
3.2
Wiring Requirements for the Drive
Certain drive requirements should be checked before continuing with the drive installation. Wire
sizes, branchcircuit protection, speed feedback (for vector regulation), and E-stop wiring (see
chapter 7), are all areas that need to be evaluated.
3.2.1 Meeting Terminal Strip Input and Output Specifications
The terminal strip on the Regulator board provides terminals for 24 VDC power for the eight remote
control inputs. Refer to tables A.3 and A.4 for control input and output specifications.
3.2.2 Determining Wire Size Requirements
Wire size should be determined based on the size of conduit openings, NEC/CEC regulations, and
applicable local codes.
THE USER IS RESPONSIBLE FOR CONFORMING WITH ALL APPLICABLE LOCAL, NATIONAL, AND
INTERNATIONAL
CODES.
WIRING
PRACTICES,
GROUNDING,
DISCONNECTS,
AND
OVERCURRENT PROTECTION ARE OF PARTICULAR IMPORTANCE. FAILURE TO OBSERVETHIS
PRECAUTION COULD RESULT IN SEVERE BODILY INJURY OR LOSSOF LIFE.
3.2.2.1 Conduit Entry Opening Sizes
It is important to accurately determine the size of the conduit openings so that the wire planned for a
specific entry point will fit through the opening. Conduit opening sizes are shownin figures 4.1
through 4.6.
3.2.2.2 Recommended Power Wire Sizes
Input power wiring should be sized according to applicable codes to handle the drive's
continuous-rated input current. Output wiring should be sized according to applicable codes to
handle the drive's continuous-rated output current. See tables 3.3 through 3.7 for recommended
power wire sizes.
Table 3.3 - Recommended Power Wire Sizes for 1-10 HP Drives
Type of Wiring
Terminals
Size of Wire (Maximum)
A-C Input Power
R/L1, S/L2, T/L3
Output Power
U/T1, V/T2, W/T3
12 AWG, 3 (mm?)
D-C Input Power
+, 7
Table 3.4 - Recommended Power Wire Sizes for 15-25 HP Drives
Type of Wiring
Terminals
Size of Wire (Maximum)
A-C Input Power
R/L1, S/L2, T/L3
Output Power
U/T1, V/T2, W/T3
6 AWG, 13 (mm?)
D-C Input Power
+, 7
3-5

Advertisement

Table of Contents
loading

Table of Contents