Table 7.1 - Wiring Signal and Control I/O to the Terminal Strip (Continued)
Terminal
Number
Description
Parameters/Wiring Connections
Wiring the Output Status Relays
28
Normally-Closed Contact
Both Form A and Form B contacts are rated for
(Form B)
250 VAC/30 VDC at 5 ampsresistive or 2 ampsinductive
29
Normally-Closed Contact
load.
Common (Form B)
30
Normally-Open Contact
The following parameter must be set:
(Form A)
31
Normally-Open Contact
P013: Output Relay Configuration
Common (Form A)
Note that depending on the setting of parameter P013, the
relay coil will energize (the normally-open contactwill close
and the normally-closed contactwill open). Refer to the
GV3000 Programming instruction manual (D2-3339) for
more information.
NC,
NO.
COM
COM
"]
QSOS
USER SUPPLIED
DEVICE
PARAMETER P.013 SELECTS OUTPUT
INDICATION
7-15