Table 7.1 - Wiring Signal and Control I/O to the Terminal Strip (Continued)
Terminal
Number
Description
Parameters/Wiring Connections
Wiring a Forward/Reverse Input
19
Digital Input 6
Digital input 6 is control function programmable through
(Default - Forward/Reverse)
parameter P007. The following parameters must be set:
P.000: Control Source
P006: Second Menu Password
P007: Terminal Strip Digital Inputs Configure (Selects
and assigns a control function to digital inputs 6
to 8).
P008: Terminal Strip Speed Reference Source (Analog,
Motor Operated Potentiometer (MOP), or
Preset Speeds)
P027: Reverse Disable
Note that based on the settings of parameters P.000, P007,
P008, and 1.030 if an RMI board is used, the following
parameters can affect digital input 6.
P.023: MOP Accel/Decel Time
P024: MOP Reset Configuration
P031 to R038: Preset Speeds 1-8
Refer to the GV3000 Programming instruction manual
(D2-3339) for additional information.
16
19
FOR
REV
P.027 = ON (ENABLED)
FORWARD DIRECTION ONLY
Terminal 19 On = Reverse Direction
Diagram showsfactory setting. From the pulse tachometer
end of the motor, clockwiserotation indicates forward mo-
tor movement.
7-12