Series connection with Y-distributors
The series connection is shown here based on the example of the version with plug connector M12. The switches are con-
nected one behind the other with the aid of pre-assembled connecting cables and Y-distributors. If a safety door is opened
or if a fault occurs on one of the switches, the system shuts down the machine.
12.2.1. Maximum cable lengths
For devices with IMP/IMM inputs, switch chains are permitted up to a maximum overall cable length of 200 m taking into
account the voltage drop as a result of the cable resistance (see table below with example data and case example).
u
= 24 V -20%
n
CES-I-BR # 1
n
Max. number of switches
5
6
10
28
l
=200 m
max
l
2
l
n
CES-I-BR # n-1
CTP/CTA-BR-...-SAB # n
Possible output current per channel FO1A/FO1B
l
1
u
= 24 V -10%
min
I
out
5 x 0,34 mm
2
I
(mA)
FO1A/FO1B
10
25
50
100
150
10
25
50
100
150
10
25
50
100
150
(translation of the original operating instructions) MAN20001654-01-03/23
SPS
PLC
l
(m)
1
Max. cable length from the last switch to the
control system
150
100
80
50
25
120
90
70
50
25
70
60
50
40
25