Requirements For Connecting Cables - EUCHNER CTP-L1-BR Unicode Operating Instructions Manual

Transponder-coded safety switch with guard locking
Table of Contents

Advertisement

Operating Instructions
Transponder-Coded Safety Switch CTP/CTA-L1/2-BR
10.4.

Requirements for connecting cables

CAUTION
Risk of damage to equipment or malfunctions as a result of incorrect connecting cables.
Use connection components and connecting cables from EUCHNER.
Ì
On the use of other connection components, the requirements in the following table apply. EUCHNER
Ì
provides no warranty for safe function in case of failure to comply with these requirements.
Observe the following requirements with respect to the connecting cables:
For safety switches CTP/CTA-...-BR-...-SAB-... with plug connectors 2 x M12
Parameter
Conductor cross-section, min.
R max.
C max.
L max.
Recommended cable type
For safety switches CTP/CTA-...-BR-...-SA-... with plug connector M12, 8-pin
Parameter
Conductor cross-section, min.
R max.
C max.
L max.
Recommended cable type
For safety switches CTP/CTA-...-BR-...-SH-... with plug connector M23 (RC18)
Parameter
Conductor cross-section, min.
R max.
C max.
L max.
Recommended cable type
20
Value
0.25
60
120
0.65
LIYY 8 x 0.25 mm² or 5 x 0.34 mm²
Value
0.25
60
120
0.65
LIYY 8 x 0.25 mm²
Value
0.25
60
120
0.65
LIFY11Y min. 19-core
(translation of the original operating instructions) MAN20001654-01-03/23
Unit
mm²
W/km
nF/km
mH/km
Unit
mm²
W/km
nF/km
mH/km
Unit
mm²
W/km
nF/km
mH/km