Transponder-Coded Safety Switch CTP/CTA-L1/2-BR
10.7.

Notes on operation with safe control systems

Observe the following guidelines for connection to safe control systems:
Use a common power supply for the control system and the connected safety switches.
Ì
A pulsed power supply must not be used for UB. Tap the supply voltage directly from the power supply unit. If the power
Ì
supply is connected to a terminal of a safe control system, this output must provide sufficient electrical current.
Always connect inputs FI1A and FI1B directly to a power supply unit or to outputs FO1A and FO1B of another EUCHNER
Ì
BR device (series connection). Pulsed signals must not be present at inputs FI1A and FI1B.
The safety outputs FO1A and FO1B can be connected to the safe inputs of a control system. Prerequisite: The input must be
Ì
suitable for pulsed safety signals (OSSD signals, e.g. from light grids). The control system must tolerate test pulses on the
input signals. This normally can be set up by parameter assignment in the control system. Observe the notes of the control
system manufacturer. For the test pulse duration of your safety switch, refer to chapter 16. Technical data on page 39.
A detailed example of connecting and setting the parameters of the control system is available for many devices at
www.euchner.com in the area Downloads/Applications/CTP... or CTA.... The features of the respective device are dealt
with there in greater detail.
10.8.

Connection without and with IO-Link communication

10.8.1. Series connection without IO-Link communication

Only the safety and monitoring outputs are switched with this connection method.
With a series connection, the safety signals are looped through from device to device.

10.8.2. Series connection with IO-Link communication

If, in addition to the safety function, detailed monitoring and diagnostic data are to be processed, a BR/IO-Link Gateway is
required. To poll the communication data from the connected devices, communication connection C is routed to the BR/
IO-Link Gateway.
You will find further information in the operating instructions for your BR/IO-Link Gateway.