Battery specifications

Feature
Type
Voltage

Average battery runtime

Average battery runtimes are approximate and vary depending on connected equipment, configuration, battery age,
temperature, and so on. These estimates are based on the batteries at beginning of life.
Table 1: G2 R5000 battery runtimes
Load %
10
20
40
60
80
100
Table 2: G2 R6000 battery runtimes
Load %
10
20
40
60
80
100

Environmental specifications

Feature
Operating temperature
Nonoperating temperature
Specification
12VDC, sealed, maintenance-free, rechargable, valve-regulated, lead-acid batteries
with a 3-year service life at 25ºC (77ºF)
The battery modules have a battery string voltage of 180 V.
Estimated battery runtime
(minutes)
73
42
17
9
5
3
Estimated battery runtime
(minutes)
57
34
14
7
5
3
Specification
0ºC to 40ºC (32ºF to 104ºF)
With batteries—0ºC to 40ºC (32ºF to 104ºF)
Without batteries—-15ºC to 60ºC (5ºF to 140ºF)
Runtime with one ERM
(minutes)
245
149
69
39
25
20
Runtime with one ERM
(minutes)
202
125
57
32
22
16
Runtime with four ERMs
(minutes)*
931
559
250
144
103
80
Runtime with four ERMs
(minutes)*
753
448
194
116
84
58
Table Continued