Ups Does Not Start; I/O Bad Wiring - HPE G2 R5000 3U User Manual

Table of Contents

Advertisement

UPS does not start

Symptom
The UPS does not power up.
Solution 1
Cause
The input source is not connected correctly.
Action
Check the input connections.
Solution 2
Cause
The RPO switch is active or the RPO connector is missing.
Action
If the UPS status menu displays the "Remote Power Off" notice, inactive the RPO input.

I/O bad wiring

Symptom
I/O LED is on and there is a continuous beep.
Cause
I/O cables are not connected to the correct terminal blocks.
Action
Correctly connect the I/O cables.