3. Installation
3.2 Battery module connection
This operation must be performed when the UPS is switched off and unplugged from the AC source. In addition, do not dis-
connect the connector while the unit is operating from the AC source or in reserve mode.
Note: Before starting the UPS, connect the internal battery. A small amount of arcing may occur when connecting the batte-
ries.This is normal and does not damage the UPS or present any safety concern.
Installing the new battery module
Perform the removal instructions in reverse order.
● To ensure safety and high performance, only use batteries supplied by HPE.
● Take care to firmly press together the two parts of the connector during remounting.
Page 14
A
C
B
Connect the battery module.
A
Never pull on the wires.
Slide the left-hand side of the bezel to the
B
right. Ensure that the push button locks.
Attach the center panel.
C
792519-001 Edition 2