November 2023
5. Set the 4-20 mA signal to the desired value for when the valve is to be open.
6. Enter this value into the Commanded mA Signal text box and press Next.
Figure 15. Fisher easy-Drive Configuration Software
7. If the Close and Open values are as expected, press Confirm to accept these values. If not, press Cancel to restart
the process.
Note
The value of the 4-20 mA signal must have at least 4 mA difference between the close and open signals. A differential less than
that amount will cause the actuator to reject the calibration and use the previous values.
Should the entered values vary more than 10% from the expected 4-20 mA values; the actuator will accept the calibration and a
Notification displaying "Questionable Analog Calibration" will result.