KSB CalioTherm Pro 25 Installation & Operating Manual page 56

Circulator / high-efficiency drinking water pump
Table of Contents

Advertisement

Parameter description
Modbus baud rate
Modbus address
Modbus parity
6
Further information in the KSB ServiceTool supplementary operating manual (reference number 1157.801)
56 of 76
7 Operation
Register
Length
Type/format
[byte]
0B B8
00 02
UNIT16
0B B9
00 02
UINT16
0B BA
00 02
UINT16
Data points
Data points of type R are read-only; data points of type R/W are read enabled & write
enabled.
Table 29: Read and write data points
Function
Read
Write
All registers (07 D0 ... 07 DE) can be read out via function code 0×03 (Read holding
registers) as one unit.
Table 30: Error value key
Error value
Description
Error value, bit code
E01
Temperature limit exceeded
E03
Internal error
E05
Temperature increase, speed decrease
E06
Mains voltage too high / too low
6)
E11
Broken wire NTC / speed decrease
E13
Pump size not selected
I14
Both pumps programmed as "left pump"
Error value 2, bit code
I18
Externally forced flow in pumping direction
I19
Backflow through the pump
CalioTherm Pro
Unit
0 = 19,200 (factory setting)
2 = 4,800
3 = 9,600
4 = 19,200
5 = 38,400
6 = 57,600
7 = 115,200
0 - 247, default address 17
2 = PE: Parity Even (factory set-
ting)
1 = PO: Parity Odd
0 = P-: No Parity
Function code
Function code 03 (0×03 Read holding registers)
Function code 16 (0×10 Write multiple register)
Access
R/W
R/W
R/W
Bit
0
1
2
3
4
5
6
7
8
10
11
12
14
15
9
13
0
1
2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Caliotherm pro 80

Table of Contents