Floor Sensor Calibration
Mon 11:15
23.5
°
17:00
Manual
Other...
Mon 11:15
Actual Floor Temp.
1
24.3°
23.5
°
17:00
6
7
6
Manual
Other...
Heating Schedule
Heating Schedule
Adaptive Function
Heating Schedule
Energy Use
Energy Use
Open Window
Energy Use
User Settings
User Settings
Floor sensor calibrated
2
Sensor Application
Adaptive Function
Engineer Settings
User Settings
Engineer Settings
Sensor Type
Open Window
Engineer Settings
Floor Sens. Calibr.
Sensor Application
Adaptive Function
Sensor Type
Room Sens. Calibr.
3
Temp. Scale
Floor Sens. Calibr.
Open Window
Factory Reset
Sensor Application
Room Sens. Calibr.
Sensor Type
Temp. Scale
Floor Sens. Calibr.
Factory Reset
Current reading from
Room Sens. Calibr.
floor sensor is
23.2°
Temp. Scale
Calibrate sensor?
Factory Reset
4
PAGE 49
This option allows you to calibrate the floor sensor .
1
You should calibrate the sensor if the temperature reading differs from the actual
floor temperature .
Note that changes in the floor sensor characteristics may damage certain floors .
You can calibrate the sensor with +/- 10°C in steps of 0 .5°C in the following way:
1 . Tap the "Menu" button on the home screen .
2 . Then tap the "Engineer Settings" button .
3 . Scroll down and tap the "Floor Sensor Calibration" button .
4 . Confirm that you want to calibrate the sensor with "√" or cancel with "X" .
5 . If "√" is chosen, you must then offset the thermostat to reflect the floor
temperature actually measured .
6 . Use the "Up Arrow" or "Down Arrow" button to set the measured floor
temperature .
7 . Confirm the value with "√" . A confirmation screen will be displayed briefly .
8 . The thermostat will automatically return to "Engineer Settings" .
<
>