Advertisement

Item
7-4.
4-2) Hot water supply and heating fan control
Outdoor unit
control
1) The TE sensor, TO sensor and operation frequency control the outdoor fan.
(The minimum W1 to the maximum are controlled according to the table below.)
2) For 3 minutes after the start, the maximum fan tap for each zone that is shown in the following table is fixed. After
that, the fan is controlled according to the TE sensor temperature.
3) If TE ≥ 24 (30)* °C continues for 5 minutes, the operation stops. No error code is displayed for this; the status is the same
as the usual thermostat off. The operation restarts after 150 seconds. This intermittent running is not abnormal.
* ( ): 801, 1101
NOTE
If the heat-pump was thermo-off, the out-door fan motor (up/down) continue to run 10 min with W3 rotation.
When the water pump of hydro unit turns on, the fan motor will operate sensing value of outside air temperature (TO).
TE [°C]
A
B
C
D
401, 601
Temperature range
25°C ≤ TO < 30°C
20°C ≤ TO < 25°C
10°C ≤ TO < 20°C
5°C ≤ TO < 10°C
-3°C ≤ TO < 5°C
-10°C ≤ TO < -3°C
801, 1101
Temperature range
25°C ≤ TO < 30°C
20°C ≤ TO < 25°C
10°C ≤ TO < 20°C
5°C ≤ TO < 10°C
-3°C ≤ TO < 5°C
-10°C ≤ TO < -3°C
Operation flow and applicable data, etc.
-2 tap / 20 secs (to W1)
Stop time count
-2 tap / 20 secs (to W1)
-1 tap / 20 secs (to W1)
Number of revolutions hold
+ 1 tap / 20 secs
(Up to the maximum tap for each zone)
Less than 20 Hz
Maximum
30°C ≤ TO
W5
W6
W8
WA
WC
WC
WF
TO < -10°C
WF
TO abnormal
WF
Less than 20 Hz
Maximum
30°C ≤ TO
W4
W5
W6
W7
W9
WF
WF
TO < -10°C
WF
TO abnormal
WF
401
601
A
24
B
21
C
18
D
15
20 Hz or more to less
than 45 Hz
Maximum
W5
W6
W9
WA
WC
WC
WF
WF
WF
20 Hz or more to less
than 45 Hz
Maximum
W4
W5
W7
W8
WB
WF
WF
WF
WF
89
801
1101
30
21
18
15
45 Hz or more
Maximum
W8
WA
WC
WC
WC
WF
WF
WF
WF
45 Hz or more
Maximum
W6
W7
W8
W9
WF
WF
WF
WF
WF