Toshiba HWT-601XWHM3W-ETR Service Manual page 20

Air to water heat pump
Table of Contents

Advertisement

Unit name
Heating capacity *1 (kW)
Cooling capacity *2 (kW)
Variable range of compressor frequency
Power source
Operation mode
Electric characteristic *1 *2
Operating noise sound power level ① Hydro unit (dB (A))
Coefficient of performance *1 *2
Hydro unit
Outdoor unit
Refrigerant piping
Refrigerant
Water piping
Operating temperature range
Operating humidity range
Wiring connection
*1 Heating performance measurement conditions: outside air temperature 7°C, water supply temperature 30°C, outlet water temperature 35°C, refrigerant piping length 7.5 m (no height
difference).
*2 Cooling performance measurement conditions: outside air temperature 35°C, water supply temperature 12°C, outlet water temperature 7°C, refrigerant piping length 7.5 m (no height
difference).
*3 • The remote controller should be shipped with the hydro unit.
• Use two 1.5-meter wires to connect the hydro unit with the remote controller.
*4 Check the water piping for leakage under the maximum operating pressure.
*5 Do not leave the hydro unit at 5°C or below.
① Max operation
Heating: outside air temperature 7°C, water supply temperature 47°C, outlet water temperature 55°C.
Cooling: outside air temperature 35°C, water supply temperature 12°C, outlet water temperature 7°C.
Hydro unit
Outdoor unit
Total
Current (A)
Power (kW)
Power factor (%)
Outdoor unit (dB (A))
Outer dimension
Height (mm)
Width (mm)
Depth (mm)
Net weight (kg)
Color
Remote controller
Height (mm)
Outer dimension *3
Width (mm)
Depth (mm)
Circulation pump
Motor output (W)
Flow rate (L/min)
Type
Heat exchanger
Outer dimension
Height (mm)
Width (mm)
Depth (mm)
Net weight (kg)
Color
Compressor
Motor output (W)
Type
Model
Fan motor
Standard air capacity (m
Motor output (W)
Connection method
Hydro unit
Liquid
Gas
Outdoor unit
Liquid
Gas
Maximum length (m)
Maximum chargeless length (m)
Maximum height difference (m)
Minimum length (m)
Refrigerant name
Charge amount (kg)
Pipe diameter
Maximum length (m)
Maximum height difference (m)
Maximum working water pressure (kPa) *4
Hydro unit (°C) *5 (Cooling / Heating / Hot water)
Outdoor unit (°C) (Cooling / Heating / Hot water)
Hydro unit (%)
Outdoor unit (%)
Power wiring
Connecting line
HWT-1101XWHM3W-E, HWT-1101XWHT6W-E, HWT-1101XWHT9W-E
HWT-801H(R)W-E
8.0
6.0
10 - 90 Hz
Heating
7.05
1.54
95
40
65
5.19
23.0
Twin rotary type with DC-inverter variable speed control
3
/min)
52.4
None (Need the flow rate 13 /min or more)
3 wires: including earth wire (Outdoor unit)
19
HWT-1101H(R)W-E
11.0
8.0
10 - 100 Hz
1 phase 50 Hz 220-240 V
Cooling
Heating
8.51
10.60
1.88
2.39
96
98
40
40
63
65
3.20
4.60
720
450
235
27
White
120
120
16
60 (MAX)
16.7
32.1
Non-self-suction centrifugal pump
Plate-type heat exchange
1050
1010
370
75
Silky shade
2000
NX220A1FJ-20N
52.4
58.4
60
Flare connection
Ø6.4
Ø15.9
Ø6.4
Ø15.9
30
8
±30
5
R32
1.25
R1
±7
430
5-32 / 5-32 / 5-32
10-43 / -25-25 / -25-43
15-85
15-100
4 wires: including earth wire
Cooling
12.82
2.86
97
40
64
2.80
22.7
52.4

Hide quick links: