8-6-2. Outdoor unit
No.
Component name
Compressor
Type
DX150A1T-21F
(401HW-E, 601HW-E)
NX220A1FJ-20N
(801HW-E, 1101HW-E)
1
Outdoor fan motor
Type
ICF-140-A43-1
(401HW-E, 601HW-E)
ICF-280-A60-1
(801HW-E, 1101HW-E)
2
4-way valve coil
Type
3
DXQ-1233
Measure the resistance value of each winding with a tester.
Red
White
Black
Measure the resistance value of each winding with a tester.
Red
White
Black
Measure the resistance value.
9 ± 0.9 Ω
140
Check procedure
401HW-E, 601HW-E
Resistance
Location
value
−
Red
White
1.04 - 1.16 Ω
−
White
Black
1.04 - 1.16 Ω
−
Black
Red
1.04 - 1.16 Ω At 20°C
801HW-E, 1101HW-E
Resistance
Location
value
−
Red
White
1.16 - 1.28 Ω
−
White
Black
1.16 - 1.28 Ω
−
Black
Red
1.16 - 1.28 Ω At 20°C
401HW-E, 601HW-E
Location
Resistance value
−
Red
White
−
White
Black
−
Black
Red
801HW-E, 1101HW-E
Location
Resistance value
−
Red
White
−
White
Black
−
Black
Red
21.00 ± 1.05 Ω
32.6 ± 3.3 Ω